Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Manual Electric |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Type (drawer and fixed Air Circuit breaker) | W1-2000A | ||||
Rated Ultimate short circuit breaking capacity(KA) | Icu=80kA 400V 50KA 690V, | ||||
Ics==Icw=50kA 400V 40KA 690V, | |||||
Rated Current In (A) | 630, 800, 1000, 1250, 1600, 2000 | ||||
Number of poles | 3 poles, 4 poles | ||||
Rated Voltage Ue (V) | 400V, 690V | ||||
Rated insulation voltage Ui (A) | 1000V | ||||
Rated current of N-pole In ( A) | 50% In, 100% In | ||||
Fixed disconnection time | 23-32ms | ||||
Intelligent controller | Sandard type (M) | • • • • • • | |||
Communication Type (H) | • • • • • • | ||||
Operation Performance | Electric life | 1000 | |||
Mechanical life | Non-maintenance 2500 | ||||
Maintenance 10000 | |||||
Connection performance | Horizontal, Vertical | ||||
Weight (kg) | Drawer type 3 pole/ 4 pole | 68/77 | 70/80 | 74/81 | |
Fixed type 3 pole/ 4 pole | 42/51 | 43/52 | 45/53 |
Type (drawer and fixed Air Circuit breaker) | W1-3200A, TYW1-4000A | ||||
Rated Ultimate short circuit breaking capacity(KA) | Icu=100kA 400V 65KA 690V, | ||||
Ics==Icw=50KA 400V 50KA 690V, | |||||
Rated Current In (A) | 2000, 2500, 3200 , 4000A | ||||
Number of poles | 3 poles, 4 poles | ||||
Rated Voltage Ue (V) | 400V, 690V | ||||
Rated insulation voltage Ui (A) | 1000V | ||||
Rated current of N-pole In (A) | 50% In, 100% In | ||||
Fixed disconnection time | 23-32ms | ||||
Intelligent controller | Sandard type (M) | • • • • | |||
Communication type (H) | • • • • | ||||
Operation Performance | Electric life | 500 | |||
Mechanical life | Non-maintenance 2500 | ||||
Maintenance 10000 | |||||
Connection performance | Horizontal, Vertical | ||||
Weight (kg) | Drawer type 3 pole/ 4 pole | 94.5/117 | 94.5/117 | ||
Fixed type 3 pole/ 4 pole | 52.5/65.5 |
Type (drawer and fixed Air Circuit breaker) | W1-6300A | ||||
Rated Ultimate short circuit breaking capacity(kA) | Icu=120kA 400V 80KA 690V, | ||||
Ics==Icw=100KA 400V 65KA 690V, | |||||
Rated Current In (A) | 4000, 5000, 6300A | ||||
Number of poles | 3 poles, 4 poles | ||||
Rated Voltage Ue (V) | 400V, 690V | ||||
Rated insulation voltage Ui (A) | 1000V | ||||
Rated current of N-pole In (A) | 50% In, 100% In | ||||
Fixed disconnection time | 23-32ms | ||||
Intelligent controller | Sandard type (M) | • • • | |||
Communication type (H) | • • • | ||||
Operation Performance | Electric life | 500 | |||
Mechanical life | Non-maintenance 2000 | ||||
Maintenance 80000 | |||||
Connection performance | Horizontal, Vertical | ||||
Weight (kg) | Drawer type 3 pole/ 4 pole | 210/233 | 233 |
Intelligent Controller: