Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product Description:
Name | Unit | GW4-12 | GW4-40.5 | GW4-72.5 | GW4-126 | GW4-126G | GW4-145 | |
Rated Voltage | KV | 12 | 40.5 | 72.5 | 126 | 126 | 145 | |
Rated current | A | 200 | 630 | 630 | 630 | 630 | 630 | |
400 | 1000 | 1250 | 1250 | 1250 | 1250 | |||
630 | 2000 | 2000 | 2000 | 2000 | ||||
1000 | 2500 | 2500 | 2500 | 2500 | ||||
1250 | ||||||||
Rated short-circuit withstand current (RMS) | KA | 16 | 20 | 20 | 20 | 20 | 20 | |
20 | 31.5 | 31.5 | 31.5 | 31.5 | 31.5 | |||
25 | 40(46) | 40(46) | 40(46) | 40(46) | ||||
Rated peak withstand current (RMS) | KA | 40 | 50 | 50 | 50 | 50 | 50 | |
50 | 80 | 80 | 80 | 80 | 80 | |||
63 | 100(104) | 100(104) | 100(104) | 100(104) | ||||
1min power frequency withstand voltage (peak) | To the ground | KV | 42 | 80 | 140 | 185 | 185 | 275 |
-230 | ||||||||
Fracture | 48 | 90 | 160 | 210 | 210 | 315 | ||
-265 | ||||||||
Lightning impulse withstand voltage (peak) | To the ground | 75 | 185 | 325 | 450 | 450 | 650 | |
-550 | ||||||||
Fracture | 85 | 215 | 375 | 520 | 550 | 750 | ||
-530 | ||||||||
Terminal horizontal tension | N | 250 | 490 | 735 | 735 | 735 | 980 | |
-735 | ||||||||
Monopolar weight | KG | 60 | 80 | 200 | 240 | 240 | 300 | |
Remarks | Suitable for altitude 2000m | Suitable for 110kv altitude 4000m |
Rated Voltage | The max Rated Voltage | Rated Current | Dynamic stable current (peak value) | Thermal stable current (effective value) | One-minute power frequency voltage withstand (effective value) | Lightning shock withstand (peak value) | Open and Close Time | Terminal static tension rating | Turn off capacitive current | creep distance | Unipolar weight | Remark | |||
Earthing | Opening | Earthing | Closeing | ||||||||||||
KV | KV | A | KA | KA-S | KV | KV | S | N | A | Mm | Kg | ||||
Normal | Antifouling | ||||||||||||||
12 | 12 | 630 | 50 | 20--4 | 75 | 85 | 165 | 200 | 450 | 625 | 875 | 120 | |||
24 | 24 | 1250 | 80 | 31.5-4 | 145 | ||||||||||
1600 | 100 | 40--2 | 1225 | 170 | |||||||||||
2000 | |||||||||||||||
35 | 40.5 | 630 | 50 | 20--4 | 80 | 90 | 185 | 215 | 500 | 625 | 875 | 120 | |||
-40.5 | 1250 | 80 | 31.5-4 | 145 | |||||||||||
1600 | 100 | 40--2 | 1225 | 170 | |||||||||||
2000 | |||||||||||||||
63 | 72.5 | 630 | 50 | 20--4 | 140 | 160 | 325 | 375 | 500 | 1100 | 1600 | 180 | |||
-72.5 | 1250 | 80 | 31.5-4 | 200 | |||||||||||
1600 | 100 | 50--2 | 1813 | 225 | |||||||||||
2000 | |||||||||||||||
2500 | 125 | 20--4 | 2205 | 260 | |||||||||||
110 | 126 | 630 | 50 | 31.5-4 | 230 | 265 | 550 | 630 | 750 | 1870 | 2750 | 200 | International pressure standards in parentheses are available for altitude 2500m | ||
-126 | 1250 | 80 | -185 | -450 | -450 | -520 | 230 | ||||||||
1600 | 100 | 40--2 | 3150 | 260 | |||||||||||
2000 | |||||||||||||||
-145 | 145 | 1250 | 80 | 31.5-4 | 275 | 315 | 650 | 750 | 6+1 | Vertical 500 | 2400 | 3800 | 300 | It can be used for 110kV system with altitude of 4000m | |
1600 | 100 | 40--2 | Horizontal 170 | 320 | |||||||||||
2000 | |||||||||||||||
3150 | 125 | 50--3 | Vertical 1250 Horizontal 420 |
380 | |||||||||||
220 | 252 | 1250 | 100 | 40--3 | 450 | 530 | 1050 | 1200 | 6+1 | 1000 | 0.5 | 3740 | 5500 | 630~710 | |
-245 | 1600 | 125 | 50--3 | 6300 | 650~750 |