Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Still deciding? Get samples of $ !
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Application | |||||||||||
Universal Air circuit breaker is suitable for the circuit of AC 50Hz with rated service voltage 400V,690V and rated service current up to 6300A. It is mainly used to distribute electric energy and protect circuits and electric equipmetnagainst over-load, under-voltage, short-circuit and single-phase earthing fault. With Intelligentized and selective protection functions , the breaker can improve the reliability of power supply,and avoid unnecessary power failure. The breaker is applicable for power stations, factories and modern high-buildings, especially for the distribution system of interlligentized building. |
|||||||||||
Bitmap
|
|||||||||||
Advantages: | |||||||||||
1.By the nuclear industry conditions (1 e) experiment and Marine conditions, It's available for industrial ,land use, Marine, nuclear, wind,( - 40 ºC, hot and humid with TH type) | |||||||||||
2.Passed the CE certification of German Rhine company | |||||||||||
3.3. Obtain an internationally recognized CB certificate | |||||||||||
4.4. Intelligent, zero-flight arc and isolation function | |||||||||||
5.High breaking and short term tolerance | |||||||||||
6.Rated limited short circuit breaking capacity(Icu): 400V:80kA~120kA:690V:50kA~75kA | |||||||||||
7.Rated Operation breaking capacity(Ics): 400V:65kA~100kA:690V:50kA~65kA | |||||||||||
8.Rated short term tolerance current (Icw 1s):400V:50kA~100kA:690V:40kA~65kA | |||||||||||
9.It has the function of overload long delay, short circuit short delay, short circuit instantaneous and ground fault protection, which can be used for power distribution | |||||||||||
10.There are three position directions of "connection", "test" and "separation" in the drawer | |||||||||||
11.The communication circuit breaker based on modbus-rtu protocol is compatible with CN1DP adapter and CN1EG Ethernet | |||||||||||
12.The FDM3 short message notification module can be configured to realize the wireless monitoring of the breaker failure or alarm information | |||||||||||
13.1. Can be matched with FWB1 temperature alarm module to realize the connection point online overtemperature alarm | |||||||||||
Environment Conditions For Operation And Installation | |||||||||||
1.Ambient temperature:-5ºC-40ºC | |||||||||||
2.Elevation 2000m | |||||||||||
3.Relative humidity: not exceed 50% at the maximum ambient temperature of +40 , but higher relative humidity at the lower temperature, for example,90% at 20 . Special measures should be taken considering the dews on product surface due to temperaturechange | |||||||||||
4.Pollution protection:3 grade | |||||||||||
5.The breakers are tested by GB/T2423.10,can withstand vibration of frequency range 2Hz~13.2Hz,displacement ± 1mm and frequency range 13.2Hz~100Hz,acceleration ±0.7g. |
|||||||||||
6.Installing categories: IV for the main circuit III for other auxiliar y and control circuits | |||||||||||
7.The breaker is suitable in electromagnetic environment A; | |||||||||||
8.Damp heat type TH breakers are tested by GB/T2423.4 GB/T2423.18,can bear the influence of moisture inthe air of salt fog andoil fog ormould. | |||||||||||
9.The vertical gradient isn'tmore than5° | |||||||||||
10.There must be not any explosive medium, and there must be not any gas which would corrode metal or any conducting dust which would destory the insulation | |||||||||||
11.The circuit breaker should be installed in the compartment of switchgear cabinet and doorframe shouldbe fixedadditionally. Protectiongrade up to IP40 | |||||||||||
12.Sevice condition: The breakers are tested by GB/T 2423.1 and GB/T2423.2,ambient temperature lower -25 ,higher+70 temperature over +40 ,the breakers areused by reducing capacity;please seeing power consumption and capacitylowering coefficient ;Elevation over 2000m,the breakers are used by reducing capacity,please seeing capacity-reducing for high-elevation . |
|||||||||||
13.Storage condiction:ambient temperature -40ºC~+70ºC. |
Type (drawer and fixed Air Circuit breaker) | W1-2000A | ||||
Rated Ultimate short circuit breaking capacity(KA) | Icu=80kA 400V 50KA 690V, | ||||
Ics==Icw=50kA 400V 40KA 690V, | |||||
Rated Current In (A) | 630, 800, 1000, 1250, 1600, 2000 | ||||
Number of poles | 3 poles, 4 poles | ||||
Rated Voltage Ue (V) | 400V, 690V | ||||
Rated insulation voltage Ui (A) | 1000V | ||||
Rated current of N-pole In ( A) | 50% In, 100% In | ||||
Fixed disconnection time | 23-32ms | ||||
Intelligent controller | Sandard type (M) | • • • • • • | |||
Communication Type (H) | • • • • • • | ||||
Operation Performance | Electric life | 1000 | |||
Mechanical life | Non-maintenance 2500 | ||||
Maintenance 10000 | |||||
Connection performance | Horizontal, Vertical | ||||
Weight (kg) | Drawer type 3 pole/ 4 pole | 68/77 | 70/80 | 74/81 | |
Fixed type 3 pole/ 4 pole | 42/51 | 43/52 | 45/53 | ||
Type (drawer and fixed Air Circuit breaker) | W1-3200A, TYW1-4000A | ||||
Rated Ultimate short circuit breaking capacity(KA) | Icu=100kA 400V 65KA 690V, | ||||
Ics==Icw=50KA 400V 50KA 690V, | |||||
Rated Current In (A) | 2000, 2500, 3200 , 4000A | ||||
Number of poles | 3 poles, 4 poles | ||||
Rated Voltage Ue (V) | 400V, 690V | ||||
Rated insulation voltage Ui (A) | 1000V | ||||
Rated current of N-pole In (A) | 50% In, 100% In | ||||
Fixed disconnection time | 23-32ms | ||||
Intelligent controller | Sandard type (M) | • • • • | |||
Communication type (H) | • • • • | ||||
Operation Performance | Electric life | 500 | |||
Mechanical life | Non-maintenance 2500 | ||||
Maintenance 10000 | |||||
Connection performance | Horizontal, Vertical | ||||
Weight (kg) | Drawer type 3 pole/ 4 pole | 94.5/117 | 94.5/117 | ||
Fixed type 3 pole/ 4 pole | 52.5/65.5 | ||||
Type (drawer and fixed Air Circuit breaker) | W1-6300A | ||||
Rated Ultimate short circuit breaking capacity(kA) | Icu=120kA 400V 80KA 690V, | ||||
Ics==Icw=100KA 400V 65KA 690V, | |||||
Rated Current In (A) | 4000, 5000, 6300A | ||||
Number of poles | 3 poles, 4 poles | ||||
Rated Voltage Ue (V) | 400V, 690V | ||||
Rated insulation voltage Ui (A) | 1000V | ||||
Rated current of N-pole In (A) | 50% In, 100% In | ||||
Fixed disconnection time | 23-32ms | ||||
Intelligent controller | Sandard type (M) | • • • | |||
Communication type (H) | • • • | ||||
Operation Performance | Electric life | 500 | |||
Mechanical life | Non-maintenance 2000 | ||||
Maintenance 80000 | |||||
Connection performance | Horizontal, Vertical | ||||
Weight (kg) | Drawer type 3 pole/ 4 pole | 210/233 | 233 |