1.Product description
Gas insulated ring main unit is for the secondary distribution network 11/17.5/24/36 kV. It is a completely sealed system with a stainless steel tank containing all live parts and switching functions. A sealed steel tank with constant atmospheric conditions ensures a high level of reliability as well as personnel safety and a virtually maintenance-free system.
4.Standards
IEC 62271-100 high voltage alternating current circuit breakers6.The main technical date
Item | Unit | Switch | Switch-fuse | Vacuum circuit-breaker |
Rated voltage | kV | 24 | 24 | 24 |
Power frequency withstand voltage | kV | 50 | 50 | 50 |
Impulse withstand voltage | kV | 125 | 125 | 125 |
Rated current | A | 630 | 2001) | 200 |
Breaking capacities: | ||||
active load | A | 630 | ||
closed loop | A | 670 | ||
off load cable charging | A | 141 | ||
off load transformer | A | 20 | ||
earth fault | A | 160 | ||
earth fault cable charging | A | 91 | ||
short-circuit breaking current | kA | see 2) | 16 | |
Making capacity | kA | 40 | see 2) | 40 |
Short time current 0,5 sec | kA | 16 | ||
Short time current 1 sec | kA | 16 | ||
Short time current 3 sec | kA | 16 |
The switch Module is a three position switch disconnector and earthing switch using SF6 gas as an arc quenching medium. The switch position is close - open - earthed. In the open position the switch satisfies the disconnector requirements. |
|
The switch-fuse module has a three position switch disconnector and earthing switch identical to the switchmodule. By means of the fuse tripping device it operates as a switchfuse combination. There is a double earthing switch which in earthed position connects earth to both sides of the fuse-links simultaneously. Both earthing switches are operated in one operation. The switch-fuse and earthing switch is mechanically interlocked to prevent hazardous access to the fuse-links. The lower cover which gives access to the fuse-links is also mechanically interlocked with the earthing switch. |
|
The vacuum circuit-breaker module has vacuum bottles as interrupters of the current. In series with the circuit-breaker main circuit is connected a three-position disconnector / earthing switch. The operation between vacuum circuit-breaker and disconnector/ earthing switch is mechanicall |