Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
NO. | Items | Unit | Data | |
FKN12-12D/630 | FKN12-12(R)D/630 | |||
1 | Rated voltage | KV | 12 | |
2 | Rated frequency | Hz | 50 | |
3 | Rated Current | A | 630 | 1250 |
4 | Lightning impulse withstand voltage | KV | To earth and phase to phase 75, isolation fracture 85 | |
5 | 1 min power frequency withstand voltage | KA | To earth and phase to phase 42, isolation fracture 48 | |
6 | Rated thermal stability current | KA | 20(4s) | |
7 | Rated dynamic current | KA | 50 | |
8 | Rated dosing current (peak) | KA | 50 | 50 |
9 | Rated short circuit breaking current (Expected value) | KA | 31.5 | |
10 | Maximum at critical breaking current | A2S | According to the fuse characteristic curve | |
11 | Minimum breaking current | KA | According to the fuse characteristic curve | |
12 | Rated transfer current | KA | 1.5 | |
13 | Maximum breaking current (reference value) | KA | 1.8 | |
14 | Breaking the capacity of the no-load transformer | KVA | 1250 | |
15 | Rated cable charging current | A | 10 | |
16 | Rated active load current breaking times | Times | >100 | |
17 | The impactor touches the load switch opening time | S | >0.06 | |
18 | Earthing switch thermal stability current | KA | 20(2S) | |
19 | Earthing switch thermal stability current (peak) | KA | 50 | |
20 | Motor operating power supply voltage | V | AC DC 110, 220 |
No. | Name | Unit | Data |
1 | Fracture from | mm | >175 |
2 | Phase center distance | mm | 210±2 |
3 | Interphase air gap | mm | > 125 |
4 | Trip | mm | 210 |
5 | Over Trip | mm | >40 |
6 | Three-phase closing is not the same period | ms | <10 |
7 | Three-phase opening is not the same period | ms | <5 |
8 | The inherent opening time of divider exciter | ms | 40-65 |
9 | Main circuit resistance | uΩ | <300 |